PARSHALL FLUME CALIBRATION FOR HYDROGRAPH MEASUREMENT
 
DOI: 10.14415/konferencijaGFS 2015.072
UDC: 532.57
CC-BY-SA 4.0 license
Author : Gabrić, Ognjen; Hovány, Lajos; Horvat, Mirjana; Horvat, Zoltan
 
 Summary:
 For a b=0.0254 m wide Parshall flume, literature provides the dependence of flowrate and water depth in the throat within the flowrate range of 0.13-4.38 l/s. Volumetric measurements of flow (flow range 0 – 3 l/s) and water level measurements with ultrasonic transmitter prove that hydrograph can be determined using equation (2) (within accuracy range of -5.36 to +4.99%), or with equations (4) and (5) (within accuracy range of -3.46 to +4.77%) for water temperatures of 11.5-16oC.
 
 Keywords:
 accuracy, calibration, Parshall flume, free flow, ultrasonic transmitter